Final | 4/25/2014 | 4/25/2014 | 4/25/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson final ok
|
Final | 4/23/2014 | 4/24/2014 | 4/24/2014 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson no access to bottom floor s.east corner. Open ground in dnst. bathroom plug, no receptacle in o/s box northeast exterior box, need lockoffs on circuit breakers for double oven, microwave and furnace. 210.52 (C) (3) in kitchen peninsular countertop receptacle required
|
Rough-In Permanent Service | 11/25/2013 | 11/26/2013 | 11/26/2013 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/25/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/25/2013 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|