Final | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | PASS |
Eric Story
|
|
|
call for access; David Phone #: ###-#### final ok
|
Electrical Rough-In | 9/22/2014 | 9/22/2014 | 9/22/2014 | P | PASS |
Rex Boyles
|
|
|
David Phone #: ###-#### corrections made r/i ok
|
Electrical Rough-In | 9/18/2014 | 9/19/2014 | 9/19/2014 | A | FAIL |
Rex Boyles
|
|
|
David// please for access code Phone #: ###-#### 100amp sub main needs to be in lower position of panel. staple NM cable as per 334.30. 11/4' from edge of bored hole to edge of stud 300.4(A)(1). recetacle required so at no point along wall is more than 6 foot 210.52 (A) (1)
|
Rough-In Permanent Service | 12/16/2013 | 12/16/2013 | 12/16/2013 | P | PASS |
Rock A. Hudson
|
|
|
p/s o/h n ok
|
Temporary Service | 12/13/2013 | 12/16/2013 | 12/16/2013 | A | CANC |
Rock A. Hudson
|
|
|
Installed new meter/main panel on rear of house (northwest corner)for temporary power with weatherproof WR/TR GFCI outlet. 2 ground rods. Phone #: ###-#### >> Inspection requested via web by David McClellan Needed permenant service. Called permit desk to confirm permit was upgraded.
|
Permanent Service | 12/16/2013 | 12/16/2013 | 12/16/2013 | P | PASS |
Rock A. Hudson
|
|
|
Installed new meter/main panel on rear of house (northwest corner)for temporary power with weatherproof WR/TR GFCI outlet. 2 ground rods. Phone #: ###-#### >> Inspection requested via web by David McClellan Called permit office to get information changed for permenant service. p/s o/h n ok
|
Final | 12/13/2013 | 12/16/2013 | 12/13/2013 | A | CANC |
Rock A. Hudson
|
|
|
Installed new meter main on rear of house (northwest corner)with exterior WR/TR GFCI weatherproof outlet/circuit for temporary power. Idaho Power to move overhead service from existing location to new riser. Have already consulted with Idaho Power for height and location approval. Phone #: ###-#### >> Inspection requested via web by David McClellan Inspection cancelled from web by: David McClellan
|
Issue PAID IN FULL permit | | | 12/12/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/12/2013 | | DONE |
|
|
|
This permit was created on the web by David McClellan
|