Final | 1/30/2014 | 1/30/2014 | 1/30/2014 | P | PASS |
Rock A. Hudson
|
|
|
Lockbox is 3811. Thank You Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
|
Electrical Rough-In | 1/14/2014 | 1/15/2014 | 1/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
Lockbox code is 3811. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Back building rough in ok cover
|
Permanent Service | 1/14/2014 | 1/14/2014 | 1/14/2014 | P | PASS |
Rock A. Hudson
|
|
|
Lockbox code is 3811. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s o/h rec ok
|
Permanent Service | 12/17/2013 | 12/17/2013 | 12/17/2013 | P | FAIL |
Bob Reichert
|
|
|
Lock box 3811, Please leave detailed red tag for insurance company, let me know if you have any questions. Thanks Clay ###-#### Phone #: ###-#### >> Inspection requested via web by Clay Morgan left correction notice, BCC no violations shall be retained, NEC 240.24(D) panel shall not be in closet, 250 shall bring grounding up to code, 210 shall provide current outlet spacing and gfci protection, 358 shall strap EMT per code
|
Issue PAID IN FULL permit | | | 12/17/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/17/2013 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|