Final | 4/30/2014 | 4/30/2014 | 4/30/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by ron spen cer Final ok
|
Final | 4/29/2014 | 4/29/2014 | 4/29/2014 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by ron spen cer fix kitchen outlet to be GFci protected
|
Final | 12/23/2013 | 12/23/2013 | 12/23/2013 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by ron spen cer Needed rough in inspection
|
Rough-In Permanent Service | 12/23/2013 | 12/23/2013 | 12/23/2013 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by ron spen cer Rough in ok cover p/s u/g n ok
|
Electrical Rough-In | 12/20/2013 | 12/20/2013 | 12/20/2013 | P | FAIL |
Rock A. Hudson
|
|
|
roughin and service inspection on house. roughin only for cover on detached garage. Phone #: ###-#### >> Inspection requested via web by ron spen cer 338 refers to 334 part to for support of SE cable. 334.30- SE Cable shall have supports not exceeding 4 1/2 feet. 300.4 Where NM cable is ran through bored holes which pass less than 1 1/4" from framing member surface cable shall be protected be nail plate. 334.30- NM cable shall be secured with in 12" of entering boxes. 334.30- Flat cables shall not be stapled on edge. Garage OK cover
|
Issue PAID IN FULL permit | | | 12/20/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/20/2013 | | DONE |
|
|
|
This permit was created on the web by ron spen cer
|