Final | 2/6/2014 | 2/6/2014 | 2/6/2014 | A | PASS |
Daryl DeGrange
|
|
|
6933 garage code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey correction done, final ok
|
Final | 2/4/2014 | 2/5/2014 | 2/5/2014 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 6933 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey 210.52- Minimum required receptical outlets not compliant in master bed. 17' between outlets.
|
Rough-In Permanent Service | 12/31/2013 | 12/31/2013 | 12/31/2013 | P | PASS |
Daryl DeGrange
|
|
|
>> Inspection requested via web by Neal Rumsey correction done, rough-in p/s u/g n ok
|
Rough-In Permanent Service | 12/30/2013 | 12/30/2013 | 12/30/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC 210.52 (A)(1) receptacle spacing, receptacle required under breakfast bar. Branch circuits ran through bored holes, NEC only allows up to three NM cable per hole for heat disapation
|
Issue PAID IN FULL permit | | | 12/30/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/30/2013 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|