Final | 6/4/2014 | 6/5/2014 | 6/5/2014 | A | PASS |
Bob Reichert
|
|
|
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey ok final
|
Final | 6/2/2014 | 6/3/2014 | 6/3/2014 | A | FAIL |
Bob Reichert
|
|
|
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left message, left correction notice, NEC 210.8 outside receptacles shall be gfci protected, 406.4 shall securely mount receptacles, garage, down stairs, 404.9 shall install cover plate for switch
|
Rough-In Permanent Service | 1/20/2014 | 1/21/2014 | 1/21/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 1/17/2014 | 1/17/2014 | 1/17/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey 300.4- Conduits containing conductors larger that #4 shall have bushing. Replace broken bushing on service riser. 300.4- nail plates required where bored holes are less than 1 1/4" from framing surface. holes bored at 45 degree angle around corners in kitchen and down east wall. 334.30 NM cable shall be secured with in 12" of box. basement east wall. Down bath east- bath fan not made up.
|
Issue PAID IN FULL permit | | | 1/17/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/17/2014 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|