Final | 3/20/2014 | 3/20/2014 | 3/20/2014 | P | PASS |
Rock A. Hudson
|
|
|
Mike Phone #: ###-#### Final ok
|
Final | 3/19/2014 | 3/19/2014 | 3/19/2014 | P | FAIL |
Rex Boyles
|
|
|
Mike Phone #: ###-#### 210.8 all receptacles on kitchen counter tops shall be GFI protected
|
Final | 3/18/2014 | 3/19/2014 | 3/19/2014 | A | PART |
Rex Boyles
|
|
|
Mike Phone #: ###-#### washer and dryer power final ok
|
Change Status to I | | | 3/19/2014 | | DONE |
Christina Prado
|
|
|
To final kitchen
|
Final | 2/25/2014 | 2/25/2014 | 2/25/2014 | P | FAIL |
Rex Boyles
|
|
|
Mike Phone #: ###-#### BCC-4-05-32-code violation not to be retained. Open light boxes devices,etc. remember spark rings in kitchen devices in tile NEC 314.20.
|
Electrical Rough-In | 2/4/2014 | 2/4/2014 | 2/4/2014 | P | PASS |
Rock A. Hudson
|
|
|
mike Phone #: ###-#### washer/ dryer wall rough in ok cover
|
Application received | | | 2/4/2014 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/4/2014 | | DONE |
|
|
|
|