Electrical Rough-In | 2/28/2014 | 2/28/2014 | 2/28/2014 | A | PASS |
Bob Reichert
|
|
|
Gate will be opened and garage door will be unlocked for access. Call if you have any questions. Thank you and have a wonderful day Phone #: ###-#### >> Inspection requested via web by daniel bibikov corrections made, ri ok, see final
|
Final | 2/28/2014 | 2/28/2014 | 2/28/2014 | P | PASS |
Bob Reichert
|
|
|
Gate will be opened and garage door will be unlocked for access. Call if you have any questions. Thank you and have a wonderful day Phone #: ###-#### >> Inspection requested via web by daniel bibikov ok final
|
Electrical Rough-In | 2/27/2014 | 2/27/2014 | 2/27/2014 | P | NH |
Rock A. Hudson
|
|
|
Call half hour before coming out Phone #: ###-#### >> Inspection requested via web by daniel bibikov Wrong number listed for contact. Called contractor left message. Recall
|
Electrical Rough-In | 2/18/2014 | 2/19/2014 | 2/19/2014 | A | FAIL |
Bob Reichert
|
|
|
Back garage door will be opened Phone #: ###-#### >> Inspection requested via web by daniel bibikov called, left correction notice, NEC 300.4(A)(1) shall use nailplates for bored holes if edge of hole less than 1 1/4" from edge of framing member, 358.26 raceway system shall not have more than 360 degree total bend without pull point, 250.56 shall use 2 ground rods, 230.2 building shall be supplied by only 1 service, BCC no violations shall be retained, ri inspection requires that no devices sahll be installed
|
Final | 2/18/2014 | 2/18/2014 | 2/18/2014 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Inspection cancelled from web by: daniel bibikov
|
Issue PAID IN FULL permit | | | 2/17/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/17/2014 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|