First Notice | 3/11/2014 | 3/11/2014 | 4/4/2014 | | DONE |
Bob Reichert
|
|
|
|
Final | 3/11/2014 | 3/11/2014 | 3/11/2014 | P | PASS |
Bob Reichert
|
|
|
Brandon Phone #: ###-#### ok final, signed card
|
Final | 3/10/2014 | 3/11/2014 | 3/11/2014 | A | FAIL |
Bob Reichert
|
|
|
call for access code // Brandon Phone #: ###-#### called, left correction notice, NEC 110.12(A) shall close unused opening in panel, 110.13(A) shall securely mount equipment- lighting contactor and raceway, 330.30(B) shall secure mc cable within 12" of box above lighting contactor, 110.26(F)(1)(b) shall provide drip shield over panel, 210.8(B)(5) shall provide gfci receptacle within 6' of future sink, BCC no violations shall be retained
|
Electrical Rough-In | 2/20/2014 | 2/21/2014 | 2/21/2014 | A | PASS |
Bob Reichert
|
|
|
Brandon Phone #: ###-#### walls ok cover
|
Issue PAID IN FULL permit | | | 2/20/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Issue PAID IN FULL permit | | | 2/20/2014 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 2/20/2014 | | |
|
|
|
|