Final | 3/10/2014 | 3/10/2014 | 3/10/2014 | P | PASS |
Rex Boyles
|
|
|
All connectors changed out for "wet area" style. Through box in pump house is now a j-box, labeled and grounded. Breaker panel conduit updated for "wet area". Phone #: ###-#### >> Inspection requested via web by Pat Marvin final ok
|
Final | 3/5/2014 | 3/5/2014 | 3/5/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Trench open between well and back porch. Pumphouse on the opposite side of back porch. Phone #: ###-#### >> Inspection requested via web by Pat Marvin NEC 250.119 Identification of equipment grounding conductor shall be green NEC 314.15 EMT fittings shall be listed for wet locations NEC 300.5 conductors installed in raceways in wet locations shall be listed for wet locations
|
Electrical Rough-In | 3/5/2014 | 3/5/2014 | 3/5/2014 | P | PASS |
Daryl DeGrange
|
|
|
Trench open between well and back porch. Pumphouse on the opposite side of back porch. Phone #: ###-#### >> Inspection requested via web by Pat Marvin Rough-in ok cover trench only
|
Issue PAID IN FULL permit | | | 3/3/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/3/2014 | | DONE |
|
|
|
This permit was created on the web by Pat Marvin
|