Permit Information
Permit NumberELE14-00531
StatusFinaled
Name CME ELECTRIC
Site Address 4270 N EAGLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Provide and install lighting and power for the new building
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice7/31/20147/31/20147/14/2015 DONE
DetailsDaryl DeGrange
This permit finaled on the web by Spencer McLean
First Notice3/6/20143/6/20147/14/2015 DONE
DetailsDaryl DeGrange
This permit finaled on the web by Spencer McLean
Final7/30/20147/31/20147/31/2014APASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by Spencer McLean final ok
Final7/23/20147/23/20147/23/2014PNR
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by Spencer McLean Not ready
Permanent Service6/17/20146/17/20146/17/2014PPASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by Spencer McLean Correction done p/s u/g n ok
Electrical Rough-In6/10/20146/11/20146/11/2014APASS
DetailsDaryl DeGrange
>> Inspection requested via web by Spencer McLean Rough-in ok cover walls and hard lid.
Rough-In Permanent Service6/6/20146/6/20146/6/2014PNR
DetailsBob Reichert
Please inspect for cover Phone #: ###-#### >> Inspection requested via web by Spencer McLean met contractor, shall install mud rings, provide 1 1/4" for mc cable, strap mc ,move duct over panels, provide proper pull box at service, shall not utilize u/g at north of entry- not deep and electrical contractor did not install, and already covered
Change Status to I  3/20/2014 DONE
DetailsChristina Prado
Permit finaled by mistaje - value and permit for full Tenant build out. Seperated ELE pulled for temp service only X-REF ELE14-00552
Temporary Service3/6/20143/6/20143/6/2014PPASS
DetailsDaryl DeGrange
spencer Phone #: ###-#### corrections done, t/s u/g n ok
Temporary Service3/5/20143/6/20143/6/2014AFAIL
DetailsDaryl DeGrange
Please inspect the temporary power pole that is installed at the pad mount transformer on the East side of the site. Phone #: ###-#### >> Inspection requested via web by Spencer McLean NEC250.52(5) Grounding electrode shall not be less than 8 ft. in lenght. Full 8 ft in contact with the earth.
Issue PAID IN FULL permit  3/5/2014 DONE
Payment received via Govolutions
Owner Supplied Equipment  3/5/2014  
Application received  3/5/2014 DONE
This permit was created on the web by Spencer McLean