Temporary Service | 3/12/2014 | 3/13/2014 | 3/13/2014 | A | PASS |
Rock A. Hudson
|
|
|
Overhead temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI t/s o/h n ok
|
Final | 3/11/2014 | 3/12/2014 | 3/12/2014 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI needed temp pole inspection
|
Temporary Service | 3/12/2014 | 3/12/2014 | 3/12/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI 250.24- AC service shal have a grounding electrode conductor connected to the grounded conductor at service disconnect. Wire not landed in lug.
|
Issue PAID IN FULL permit | | | 3/11/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/11/2014 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|