Final | 5/29/2014 | 6/2/2014 | 6/2/2014 | A | PASS |
Bob Reichert
|
|
|
Swimming pool electrical. Phone #: ###-#### >> Inspection requested via web by Lars Johnson corrections made, ok final
|
Final | 4/18/2014 | 4/21/2014 | 4/21/2014 | A | FAIL |
Bob Reichert
|
|
|
swimming pool electrical Phone #: ###-#### >> Inspection requested via web by Lars Johnson pool cover not installed, fence not installed, called, asked to call back when done
|
Electrical Rough-In | 3/27/2014 | 3/28/2014 | 3/28/2014 | A | PASS |
Daryl DeGrange
|
|
|
Jarod Phone #: ###-#### correction done, rough-in ok cover underground conduits
|
Electrical Rough-In | 3/26/2014 | 3/27/2014 | 3/27/2014 | P | FAIL |
Bob Reichert
|
|
|
jarod Phone #: ###-#### called contractor, left correction notice, tried to explain u/g per NEC 680.10, conduit shall be minimum 18" deep, gave 447 phone number to call
|
Electrical Rough-In | 3/19/2014 | 3/20/2014 | 3/20/2014 | A | PASS |
Bob Reichert
|
|
|
Swimming pool bonding: - (2) autocover - (1) equipment - (1) fence Phone #: ###-#### >> Inspection requested via web by Lars Johnson pool bonding for items listed ok
|
Issue PAID IN FULL permit | | | 3/19/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/19/2014 | | DONE |
|
|
|
This permit was created on the web by Lars Johnson
|