Final | 3/12/2015 | 3/13/2015 | 3/13/2015 | P | PASS |
Bob Reichert
|
|
|
Final inspection Duplex 2 1902 and 1904. Building permit number BLD13-00195. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok final
|
Permanent Service | 9/11/2014 | 9/12/2014 | 9/12/2014 | A | PASS |
Bob Reichert
|
|
|
Country Home #2 permanent service inspection. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum p/s u/g n ok, 2 meters req'd
|
Electrical Rough-In | 8/27/2014 | 8/27/2014 | 8/27/2014 | P | PASS |
Bob Reichert
|
|
|
Need electrical rough-in for Country Home #2. Call Lonny when on site. Thanks. Phone #: ###-#### >> Inspection requested via web by Lonny Baum ri ok
|
Rough-In Permanent Service | 5/27/2014 | 5/28/2014 | 5/28/2014 | A | PASS |
Bob Reichert
|
|
|
Call Lonny when at job trailer to get escort to duplex #2 UFER inspection. Thanks Phone #: ###-#### >> Inspection requested via web by Lonny Baum ok cover concrete encased electrode, NOTE: left correction notice for duplexes, NEC 110.26(F)(1) there shall be no foreign systems in dedicated space- no piping below panels
|
Issue PAID IN FULL permit | | | 3/25/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/25/2014 | | DONE |
|
|
|
This permit was created on the web by Vicki Moore
|