Final | 9/10/2014 | 9/11/2014 | 9/11/2014 | A | PASS |
Rock A. Hudson
|
|
|
Darrell Phone #: ###-#### Final ok
|
Final | 9/4/2014 | 9/5/2014 | 9/5/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Daryl Phone #: ###-#### 410.30(B)(1)- A pole supporting luminaire shall have a accessible hand hole. 250.70- 2 east poles shall have lugs listed for multiple conductors. 358.30- EMT on outside of pole shall be securely mounted.
|
Electrical Rough-In | 5/14/2014 | 5/14/2014 | 5/14/2014 | P | CANC |
Bob Reichert
|
|
|
bonding for lighting pole bases // Daryl Phone #: ###-#### called, explained that pole base grounding is for lightning protection per desin engineer specifications, electrical requires branch circuit and equipment grounding be done at final
|
Electrical Rough-In | 5/9/2014 | 5/9/2014 | 5/9/2014 | P | PASS |
Rock A. Hudson
|
|
|
Darrel-pole base ground inspection Phone #: ###-#### Pole bases rough in ok cover
|
Electrical Rough-In | 4/15/2014 | 4/15/2014 | 4/15/2014 | P | PART |
Rock A. Hudson
|
|
|
underground - Darrell Phone #: ###-#### Underground for tennis courts rough in ok cover
|
Electrical Rough-In | 4/14/2014 | 4/14/2014 | 4/14/2014 | P | PASS |
Rock A. Hudson
|
|
|
Darrel-trenching Phone #: ###-#### parking lot underground rough in ok cover
|
Electrical Rough-In | 4/11/2014 | 4/11/2014 | 4/11/2014 | A | PART |
Rock A. Hudson
|
|
|
ground trenching Phone #: ###-#### Underground from edge of baseball field across new parking lot rough in ok cover
|
Electrical Rough-In | 4/9/2014 | 4/9/2014 | 4/9/2014 | P | CANC |
Rock A. Hudson
|
|
|
trench// Daryl Phone #: ###-#### // cancelled per Daryl, will call back to schedule. 4/9/14 @11:53, LEG called inspector.
|
Electrical Rough-In | 3/31/2014 | 3/31/2014 | 3/31/2014 | P | PASS |
Rock A. Hudson
|
|
|
eli Phone #: ###-#### Underground for lighting and recepticals around existing parking lot up to new lot area. Rough in ok cover
|
Issue PAID IN FULL permit | | | 3/27/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/27/2014 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|