Final | 5/20/2014 | 5/20/2014 | 5/20/2014 | P | PASS |
Rock A. Hudson
|
|
|
webb Phone #: ###-#### p/s o/h rec ok
|
Final | 5/19/2014 | 5/19/2014 | 5/19/2014 | P | FAIL |
Rock A. Hudson
|
|
|
rosalie Phone #: ###-#### Home owner has not called for conference as reqwested on form PDS 424-B. I requested a conference to discuss issues with service and some dangerous over head conductors to out building. Overhead conductors are at 6'9", 7'3" and 8" to out building. shall be removed due to hieght and illegal terminations. Wires shall be properly terminated exiting house. BCC 4-05-32 Code violation not to be retained. Owner's son not available to meet so sent a friend so I could inform of issues. 110.26 work platform needs 36" depth from front of service.
|
Permanent Service | 5/13/2014 | 5/13/2014 | 5/13/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Web Robertson Phone #: ###-#### Due to modifications new code violations exist. 110.26- Minimum work platform 30" wide and 36" deep. 240.24(A)- Each circuit breaker that can be installed shall be below 6'7". 250.64(B)- Where exposed a #4 minimum copper grounding electrode conductor shall be installed where subject to physical damage. 250.56- Ground rods shall be installed a minimum of 6' apart. 230.24(A)- Service mast shall clear short overhang portion of roof by minimum of 18". Tried to contact owner 2 times. sounded like voicemail was available on 2nd call but not sure if operational .
|
Final | 5/13/2014 | 5/13/2014 | 5/13/2014 | P | CANC |
Rock A. Hudson
|
|
|
Web Robertson Phone #: ###-#### Needed permenant service inspection.
|
Final | 5/9/2014 | 5/12/2014 | 5/12/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Wes (son to Rosalie) Phone #: ###-#### 250.53(D)- Underground metal pipe shall be supplemented by an additional groudning electrode. 250.53(C)- Grounding electrode bonding jumper shall be sized based on service entrance conductors, #4 minimum. 240.24(A)- Overcurrent devices shall be located so that handle of sircuit breakers do not exceed 6'7". 230.24(A)- Where overhead service mast is over 3' above roof it shall have additional support.
|
Application received | | | 4/16/2014 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/16/2014 | | DONE |
|
|
|
|
Telephone call | | | 4/16/2014 | | DONE |
Tisha Gallop
|
|
|
called Doug Poedy and authorized son(Web Robertson) to sign homeowners form for mother(parcel owner)
|