Final | 5/30/2014 | 6/2/2014 | 6/2/2014 | A | PASS |
Rock A. Hudson
|
|
|
Need final for GFI all 2 wire circuits in the home. Lock box code is 2026 Phone #: ###-#### >> Inspection requested via web by John Edwards Final ok
|
Final | 5/28/2014 | 5/29/2014 | 5/29/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Need a final for this job. Lock box code is 2026. Call jimmy @ ###-#### for questions. Phone #: ###-#### >> Inspection requested via web by John Edwards BCC 4-05-32- Code violations not to be retained. NEC 406.3(D)- Grounded type recepticals installed on ungrounded circuits shall be GFCI protected or be changed to 2-wire receptical outlets
|
Electrical Rough-In | 4/22/2014 | 4/22/2014 | 4/22/2014 | P | PASS |
Rock A. Hudson
|
|
|
Need an ok to cover walls. Home is unoccupied and a lock box is in the back on the chain link fence. the code is 2026. Phone #: ###-#### >> Inspection requested via web by John Edwards Rough in ok cover
|
Issue PAID IN FULL permit | | | 4/22/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/22/2014 | | DONE |
|
|
|
This permit was created on the web by John Edwards
|