Final | 6/30/2014 | 7/1/2014 | 7/1/2014 | A | PASS |
Rock A. Hudson
|
|
|
>> Inspection requested via web by Stacie Tasker Final ok
|
Final | 6/26/2014 | 6/27/2014 | 6/27/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Stacie Tasker 210.12- All 15 and 20 amp 120 volt outlets shall have AFCI protection. 210.52(C)(1)- A receptical outlet shall be located with in 24" of left side of range. 210.63- A 120 volt 15 or 20 amp receptical outlet shall be located with in 25' of AC unit accessible from outside. 406.11- All areas specified in 210.52 all 15 and 20 amp 120 volt receptical outlet shall be tamper resistant type.
|
Electrical Rough-In | 5/2/2014 | 5/5/2014 | 5/5/2014 | A | PASS |
Rock A. Hudson
|
|
|
>> Inspection requested via web by Stacie Tasker rough in ok cover
|
Permanent Service | 5/5/2014 | 5/5/2014 | 5/5/2014 | P | PASS |
Rock A. Hudson
|
|
|
>> Inspection requested via web by Stacie Tasker p/s u/g n ok
|
Electrical Rough-In | 5/1/2014 | 5/2/2014 | 5/2/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Idaho power requires an expansion joint on all underground service entrance conduits for residential. 250.52(B)(1)- Metal gas piping systems shall not be used as grounding electrodes. 250.104(B) not enforced in Idaho. 334.30- NM cable shall be secured with in 12" of box. 210.52- Up bedroom, any wall space 24" and wider shall have receptical outlet installed.
|
Issue PAID IN FULL permit | | | 5/1/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/1/2014 | | DONE |
|
|
|
This permit was created on the web by Stacie Tasker
|