First Notice | 6/22/2015 | 6/22/2015 | 8/25/2015 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by Shawna Gates
|
Final | 6/16/2015 | 6/22/2015 | 6/22/2015 | A | PASS |
Rex Boyles
|
|
|
Shane is the onsite contact his cell no. is ###-####. If you have any questions, please call. Phone #: ###-#### Inspection requested via web by Shawna Gates final ok
|
Electrical Rough-In | 3/30/2015 | 3/31/2015 | 3/31/2015 | P | PART |
Rex Boyles
|
|
|
Partial Final for I.T. area. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates final ok for IT area only LOOK FOR BLANK PLATE AT SINK AND BREAKER HANDLE TIES NEXT INSPECTION
|
Electrical Rough-In | 3/19/2015 | 3/20/2015 | 3/20/2015 | A | PASS |
Rex Boyles
|
|
|
Ceiling inspection. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i print shop ceilings ok
|
Electrical Rough-In | 3/17/2015 | 3/17/2015 | 3/17/2015 | P | PASS |
Rex Boyles
|
|
|
Ceiling inspection. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates I.T. ceiings ok to cover will look at exhaust fan and re feed of air-handeler at open tiles on next inspection.
|
Electrical Rough-In | 2/19/2015 | 2/19/2015 | 2/19/2015 | A | PASS |
Cevyn Recla
|
|
|
rough in wall I.T. area. Shane is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Walls OK to cover in IT area, there will be one more outlet added in office on wall that seperates office and closet when wall is replaced
|
Electrical Rough-In | 2/17/2015 | 2/17/2015 | 2/17/2015 | P | PASS |
Rex Boyles
|
|
|
Shane is the contact. His cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i cafe ceiling ok
|
Electrical Rough-In | 1/29/2015 | 1/29/2015 | 1/29/2015 | P | CANC |
Rex Boyles
|
|
|
Ceiling inspection for Annex. Shane is the contact his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Electrical Rough-In | 1/22/2015 | 1/23/2015 | 1/23/2015 | P | DONE |
Cevyn Recla
|
|
|
Final on Annex portion of the project. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates see partial final inspection, 1.23.15
|
Final | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | PART |
Cevyn Recla
|
|
|
Final on Annex portion of the project. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Partial Final, First floor , HR department area, conference room, open office area, team area, reception desk and seating area, Need to check the lights and switch in Borah room at next inspection.
|
Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 | P | PASS |
Rex Boyles
|
|
|
Ceiling inspection at print shop. Elver is the contact his cell no. is ###-####. Inspection requested via web by Shawna Gates r/i partial ceiling print shop. r/i cafe storage room and ceiling in hallway exit to 6th street
|
Electrical Rough-In | 1/13/2015 | 1/13/2015 | 1/13/2015 | P | PASS |
Cevyn Recla
|
|
|
Ceiling inspection. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Ceiling cover, light fixture change out, ok to cover
|
Electrical Rough-In | 1/9/2015 | 1/9/2015 | 1/9/2015 | P | PASS |
Rex Boyles
|
|
|
Ceiling inspection for Annex. Shane is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i annex ceilings ok to cover( not including HR ceilings) 4th floor east walls final ok
|
Electrical Rough-In | 12/15/2014 | 12/15/2014 | 12/15/2014 | P | PASS |
Rex Boyles
|
|
|
Print shop - Elver is the contact his cell no. ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i print shopwalls ok
|
Electrical Rough-In | 12/11/2014 | 12/11/2014 | 12/11/2014 | P | PASS |
Rex Boyles
|
|
|
4th floor rough in, Shane is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates r/i ok 4thfloor east wall atty's office and breakroom. r/i ok bsmt. stairwell B walls
|
Electrical Rough-In | 11/12/2014 | 11/12/2014 | 11/12/2014 | P | PASS |
Rex Boyles
|
|
|
Annex- Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i annex n.east corner of bldg. walls ok
|
Electrical Rough-In | 10/31/2014 | 10/31/2014 | 10/31/2014 | P | PASS |
Rex Boyles
|
|
|
4th floor corner office. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates s.west office low wall receptacles
|
Electrical Rough-In | 10/16/2014 | 10/16/2014 | 10/16/2014 | P | CANC |
Rex Boyles
|
|
|
Bruce Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
Electrical Rough-In | 10/8/2014 | 10/9/2014 | 10/9/2014 | P | PASS |
Rex Boyles
|
|
|
Ceiling inspection. Shane is the contact his cell no. ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i ceiling 4th flr elevator lobby ok wrote up correction notice to clean up fire alarm wiring for bruce
|
Electrical Rough-In | 9/24/2014 | 9/25/2014 | 9/25/2014 | A | PASS |
Rex Boyles
|
|
|
Please call Shane prior to inspection at ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 3rd floor so. west office chase r/i ok
|
Electrical Rough-In | 9/22/2014 | 9/23/2014 | 9/23/2014 | P | PASS |
Rex Boyles
|
|
|
3rd floor rough in cover. Shane is the contact ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 3rd floor CH2 lobby ceiling ok
|
Final | 9/22/2014 | 9/23/2014 | 9/22/2014 | P | CANC |
Rex Boyles
|
|
|
3rd Floor rough in cover. Shane is the contact ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Electrical Rough-In | 9/22/2014 | 9/22/2014 | 9/22/2014 | P | CANC |
Rex Boyles
|
|
|
3rd floor rough in cover. Shane is the contact his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Final | 9/22/2014 | 9/23/2014 | 9/22/2014 | P | CANC |
Rex Boyles
|
|
|
3rd floor rough in cover. Shane is the contact his cell no. ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Electrical Rough-In | 8/28/2014 | 8/28/2014 | 8/28/2014 | P | PASS |
Doug A Poedy
|
|
|
call Shane 1/2 hour prior .. 2nd floor CH2 elevator lobby Phone #: ###-#### >> Inspection requested via web by Mike Basye. Ok to cover ceiling.
|
Electrical Rough-In | 8/22/2014 | 8/22/2014 | 8/22/2014 | P | PASS |
Rock A. Hudson
|
|
|
Soffit 2nd floor in front of elevator. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Mike Basye CH2 soffit by elevator 2 cans rough in ok cover
|
Change Status to I | | | 7/30/2014 | | DONE |
Candy A. Nichols
|
|
|
Rex did a partial inspection on 7-21-14 and accidentially passed the final.
|
Electrical Rough-In | 7/18/2014 | 7/21/2014 | 7/21/2014 | A | CANC |
Rex Boyles
|
|
|
Partial final. CH2 1st floor West--Shane is the contact his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye needed final
|
Final | 7/21/2014 | 7/21/2014 | 7/21/2014 | P | PART |
Rex Boyles
|
|
|
Partial final. CH2 1st floor West--Shane is the contact his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye final ok CH2 1st floor west side
|
Electrical Rough-In | 7/15/2014 | 7/16/2014 | 7/16/2014 | A | PASS |
Rex Boyles
|
|
|
Please call Shane 30 min prior at ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye ceilings ok to cover in CH21st floor Arts and history
|
Electrical Rough-In | 7/1/2014 | 7/2/2014 | 7/2/2014 | P | PASS |
Rex Boyles
|
|
|
Shane is the onsite contact his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye r/i ok CH2 walls
|
Electrical Rough-In | 6/23/2014 | 6/23/2014 | 6/23/2014 | P | PASS |
Rex Boyles
|
|
|
1st floor. Call Mike 30 min prior at ###-####. Please call Brue 30 min prior at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Mike Basye rough in ceiling 1st floor lobby
|
Electrical Rough-In | 6/18/2014 | 6/19/2014 | 6/19/2014 | A | PASS |
Rex Boyles
|
|
|
Ceiling- parking garage elevator lobby. Please call Mike 30 min. prior to inspection at ###-####. Bruce Steinwinter request that you call him prior to entering the building. His cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye rough in ceiling ok CH2 BSMT Lobby
|
Electrical Rough-In | 6/3/2014 | 6/3/2014 | 6/3/2014 | P | PASS |
Rock A. Hudson
|
|
|
We need a final on the Chiller only. Contact is Shane McKissin his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye Chiller rough in ok
|
Issue PAID IN FULL permit | | | 5/9/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 5/9/2014 | | |
|
|
|
|
Application received | | | 5/9/2014 | | DONE |
|
|
|
This permit was created on the web by Mike Basye
|