Final | 5/20/2014 | 5/21/2014 | 5/21/2014 | A | PASS |
Rock A. Hudson
|
|
|
Contact: Brain Gee Phone #: ###-#### >> Inspection requested via web by Deb Gooden Final ok
|
Permanent Service | 5/15/2014 | 5/15/2014 | 5/15/2014 | P | PASS |
Rock A. Hudson
|
|
|
Contact: Cody Cannon... Entry code 2042 Phone #: ###-#### >> Inspection requested via web by Deb Gooden Due to panel labelling not complete will need to call for final when complete. p/s o/h rec ok
|
Permanent Service | 5/13/2014 | 5/14/2014 | 5/13/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Contact:Cody Cannon - entry code is 2042, call Cody with questions please Phone #: ###-#### >> Inspection requested via web by Deb Gooden 250.92(B)(4)- Where nipple enters through concentric knock out standard lock nut shall not be sole means of bonding. 110.3- Examination- 30a 2 pole breaker defective. Appears to be installed on 12 ga wire.
|
Permanent Service | 5/13/2014 | 5/13/2014 | 5/13/2014 | P | NH |
Rock A. Hudson
|
|
|
CONTACT: CODY CANNON Phone #: ###-#### >> Inspection requested via web by Deb Gooden House locked no answer at number provided.
|
Issue PAID IN FULL permit | | | 5/12/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/12/2014 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|