Final | 7/24/2014 | 7/25/2014 | 7/25/2014 | A | PASS |
Rock A. Hudson
|
|
|
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Final ok
|
Rough-In Permanent Service | 5/20/2014 | 5/21/2014 | 5/21/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 5/18/2014 | 5/19/2014 | 5/19/2014 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member, 334.23 shall protect nm cable within 6' of attic access, BCC shall terminate nm in box, shall wire boxes mounted, shall not cover front light prior to inspection
|
Issue PAID IN FULL permit | | | 5/18/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/18/2014 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|