Final | 9/5/2014 | 9/5/2014 | 9/5/2014 | P | PASS |
Rex Boyles
|
|
|
Inspection requested via web by Steve Craig corrections made final ok
|
Final | 9/2/2014 | 9/3/2014 | 9/3/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Steve Craig A/C unit requires wiring rated for wet locations, Furnace requires labeled disconnect or breaker lockout, Receptacle in wine cellar requires equipment grounding connection, Panel directory too brief.
|
Electrical Rough-In | 7/2/2014 | 7/3/2014 | 7/3/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Steve Craig r/i ok corrections made
|
Electrical Rough-In | 7/2/2014 | 7/2/2014 | 7/2/2014 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Steve Craig met builder, he called electrical contractor, contractor called, told him knob and tube wiring shall not have insulation covering it, shall fix broken box, shall not have open splices, shall not provide exceeded box fill (pan over stairs)
|
Electrical Rough-In | 7/1/2014 | 7/1/2014 | 7/1/2014 | A | FAIL |
Rex Boyles
|
|
|
Rough-in of addition. Phone #: ###-#### >> Inspection requested via web by Steve Craig 400.8 (2) flexable cords not permitted where concealed in walls ,floors or ceilings. 336.12(2) where installed outside raceway or cable tray..
|
Electrical Rough-In | 6/15/2014 | 6/16/2014 | 6/16/2014 | A | PASS |
Rex Boyles
|
|
|
Rough in of basement Phone #: ###-#### >> Inspection requested via web by Steve Craig bsmt. rough in ok except for bsmt. hallway and pantry
|
Electrical Rough-In | 6/12/2014 | 6/13/2014 | 6/13/2014 | A | FAIL |
Bob Reichert
|
|
|
Cover inspection for basement Phone #: ###-#### >> Inspection requested via web by Steve Craig called, met builder, shall staple nm within 12" of box, shall not use damaged nm, shall not staple nm on edge, shall add receptacle in 10' hall, shall secure nm out of can lights
|
Electrical Rough-In | 6/4/2014 | 6/5/2014 | 6/5/2014 | A | PASS |
Daryl DeGrange
|
|
|
Rough-in of concrete walls in basement prior to insulation and furring strips. Phone #: ###-#### >> Inspection requested via web by Steve Craig rough-in ok cover basement exterior walls
|
Permanent Service | 5/22/2014 | 5/22/2014 | 5/22/2014 | P | PASS |
Rex Boyles
|
|
|
Relocate of existing service in preparation for addition to house. Idaho Power disconnect scheduled at 9:00 am. Should be ready for inspection by 12:00. pm Phone #: ###-#### >> Inspection requested via web by Steve Craig p/s o/h rec ok
|