Information based on query as of Monday, July 8, 2024.
Permit Information
Permit NumberELE14-01319
StatusFinaled
Name LYNN PROCTOR ELECTRIC
Site Address 1950 S COLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Install new serice, wiring & GFI Recepts
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice6/27/20146/27/20149/8/2014 DONE
DetailsRock A. Hudson
Final6/26/20146/27/20146/27/2014APASS
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor Final ok
Final6/25/20146/26/20146/26/2014AFAIL
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor 511.12- All 15 and 20 amp receptical outlet shall have GFCI protection for personel.
408.4- Circuit directory shall be complete for paint booth panel
Electrical Rough-In5/22/20145/23/20145/23/2014APASS
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### on your way to the site. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor Interior surface conduits and recepticals rough in ok
Permanent Service5/22/20145/23/20145/23/2014APASS
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### on your way to the site.. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor p/s u/g n ok
Issue PAID IN FULL permit  5/22/2014 DONE
Payment received via Govolutions
Application received  5/22/2014 DONE
This permit was created on the web by Lynn Proctor