Final | 8/4/2014 | 8/5/2014 | 8/5/2014 | A | PASS |
Rock A. Hudson
|
|
|
The lock box is on the fence, the code is1225, thx. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Final ok
|
Electrical Rough-In | 6/17/2014 | 6/17/2014 | 6/17/2014 | P | PASS |
Rex Boyles
|
|
|
rough in ok corrections made
|
Rough-In Permanent Service | 6/13/2014 | 6/16/2014 | 6/16/2014 | A | FAIL |
Rex Boyles
|
|
|
Can you also inspect the depth of the trench heading towards the garage so the builder can bury, any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren front soffit never inspected prior to cover, 312.5(C) for all in one . too many cables thru 2" 2 screw connector
|
Permanent Service | 6/16/2014 | 6/16/2014 | 6/16/2014 | P | PASS |
Rex Boyles
|
|
|
Can you also inspect the depth of the trench heading towards the garage so the builder can bury, any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren p/s u/g n ok
|
Rough-In Permanent Service | 6/12/2014 | 6/13/2014 | 6/13/2014 | A | FAIL |
Bob Reichert
|
|
|
any questions I have a crew in the home next door, thx, TW., Phone #: ###-#### >> Inspection requested via web by Stephen Kren checked with contractor, left correction notice, NEC 334.23 shall protect nm cable within 6' of attic access, 210.52(A)(1)(2) shall install receptacle in 2' wall, 300.4(A) shall provide steel plate if edge of bored hole is less than 1 1/4" from edge of frqaming member, BCC shall post address or job id sticker, NOTE: no u/g from house to garage installed or inspected
|
Issue PAID IN FULL permit | | | 6/12/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/12/2014 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|