Final | 7/28/2014 | 7/29/2014 | 7/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
Call for lockbox code for access Phone #: ###-#### >> Inspection requested via web by Lars Johnson Final ok
|
Rough-In Permanent Service | 6/23/2014 | 6/24/2014 | 6/24/2014 | A | PASS |
Rock A. Hudson
|
|
|
Corrections made Phone #: ###-#### >> Inspection requested via web by Lars Johnson Rough in ok cover p/s o/h rec ok
|
Rough-In Permanent Service | 6/23/2014 | 6/23/2014 | 6/23/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Call for access if door is locked. Phone #: ###-#### >> Inspection requested via web by Lars Johnson 250.52(A)(1)- Grounding electrode conductor shall terminate on metal water piping system with in 5' of entering premisis. 314.16- 3"X2"X2" Boxes in basement shall be sufficient size for conductors and device to be installed. 358.30- EMT used for service riser shall be secured with in 3' of meter base.
|
Issue PAID IN FULL permit | | | 6/19/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/19/2014 | | DONE |
|
|
|
This permit was created on the web by Lars Johnson
|