Final | 7/26/2014 | 7/28/2014 | 7/28/2014 | A | PASS |
Rex Boyles
|
|
|
Access is 0475. Phone #: ###-#### Inspection requested via web by Paula Gratiot final ok
|
Final | 7/11/2014 | 7/14/2014 | 7/14/2014 | A | FAIL |
Rex Boyles
|
|
|
Jim talked to Rex about floors being done week of 7-14. Access code is 0475. Email address is different now. Please use energysmartwiring@gmail.com. Thanks Phone #: ###-#### >> Inspection requested via web by Paula Gratiot GFCI protection in bathroom and kitchen plugmold
|
Final | 6/30/2014 | 7/1/2014 | 7/1/2014 | A | FAIL |
Rex Boyles
|
|
|
Access code is 0475. Phone #: ###-#### >> Inspection requested via web by Paula Gratiot current panel schedule needed, exposed 120 splice to doorbell x-former, fused nuetral in furnace disconnect, no GFCI protection in bathroom and kitchen countertop plugmold and no ground, in use cover on front exterior GFCI receptacle, basement receptacles have reverse polarity and not GFCI protected within 6 ' of sink, blank plate on ceiling box at bottom of stairs
|
Issue PAID IN FULL permit | | | 6/30/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/30/2014 | | DONE |
|
|
|
This permit was created on the web by Paula Gratiot
|