Permanent Service | 7/9/2014 | 7/10/2014 | 7/10/2014 | A | PASS |
Rock A. Hudson
|
|
|
Call for access to home Phone #: ###-#### >> Inspection requested via web by Brandon Blackham p/s o/h rec ok
|
Final | 7/10/2014 | 7/10/2014 | 7/10/2014 | P | PASS |
Rock A. Hudson
|
|
|
Call for access to home Phone #: ###-#### >> Inspection requested via web by Brandon Blackham Final ok
|
Final | 7/5/2014 | 7/7/2014 | 7/7/2014 | P | CANC |
Rock A. Hudson
|
|
|
This is the Homeowners number so you can get access call him when you are on the way Jeremy is his name. Any other questions feel free to contact me at ###-#### Brandon Blackham Phone #: ###-#### >> Inspection requested via web by Brandon Blackham Needed permenant service inspection.
|
Permanent Service | 7/7/2014 | 7/7/2014 | 7/7/2014 | P | FAIL |
Rock A. Hudson
|
|
|
This is the Homeowners number so you can get access call him when you are on the way Jeremy is his name. Any other questions feel free to contact me at ###-#### Brandon Blackham Phone #: ###-#### >> Inspection requested via web by Brandon Blackham 250.53- Where single pipe or rod is used as grounding electode it shall have supplemental electrode. 210.3- Each branch circuit shall be fused. remove taps off main feeders
|
Issue PAID IN FULL permit | | | 7/5/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/5/2014 | | DONE |
|
|
|
This permit was created on the web by Brandon Blackham
|