Final | 7/24/2014 | 7/25/2014 | 7/25/2014 | A | PASS |
Daryl DeGrange
|
|
|
Please call Jake if you have any questions ###-####, thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan correction done, final ok
|
Final | 7/23/2014 | 7/24/2014 | 7/24/2014 | A | FAIL |
Daryl DeGrange
|
|
|
The key is sitting on top of the meter box, if you have any questions, please call Clay ###-####. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan NEC 210.8(B)(2)
|
Final | 7/22/2014 | 7/23/2014 | 7/23/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Key is in the breaker box. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan NEC 408.4 Shall complete panel directory, no key for access to test receptacles inside for GFCI protection
|
Final | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | NR |
Daryl DeGrange
|
|
|
Thanks. ###-#### Phone #: ###-#### >> Inspection requested via web by Clay Morgan Not ready for final at this time.
|
Permanent Service | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | PASS |
Daryl DeGrange
|
|
|
Thanks. ###-#### Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s o/h n ok
|
Permanent Service | 7/17/2014 | 7/18/2014 | 7/18/2014 | A | FAIL |
Daryl DeGrange
|
|
|
If you have any questions, please call Clay at ###-####. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan NEC 250.56 Permanent service requires two grounding electrodes. NEC 312.5(C) Prohitbits the installation of several cables bunched together. NEC 210.8 requires GFCI protection for all 15 and 20 ampere 120 volt receptacles.
|
Issue PAID IN FULL permit | | | 7/15/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/15/2014 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|
First Notice | 7/25/2014 | 7/25/2014 | | | |
Daryl DeGrange
|
|
|
|