Final | 9/29/2014 | 9/29/2014 | 9/29/2014 | P | PASS |
Daryl DeGrange
|
|
|
Key is on top of meter main at back of house for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov correction done, final ok
|
Fees Due Hold | 9/27/2014 | | 9/29/2014 | | DONE |
|
|
|
|
Final | 9/25/2014 | 9/25/2014 | 9/26/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Key is on back of house on top of meter main for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov No underground inspection recorded, NEC 334.12(B)(4) NM cable not permited in wet or damp locations underground to unattached garage
|
Final | 9/23/2014 | 9/24/2014 | 9/24/2014 | A | FAIL |
Bob Reichert
|
|
|
Key is on top of meter main for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov called, NEC 210.52(E) shall provide rear receptacle
|
Rough-In Permanent Service | 7/23/2014 | 7/24/2014 | 7/24/2014 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov correction done, rough-in p/s u/g n ok w/ detacted garage, no underground
|
Rough-In Permanent Service | 7/23/2014 | 7/23/2014 | 7/23/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov B.C.C. 04-05-23 Unlawful to conceal It shall be unlawful for any person to cover up or in any way conceal any electrical wiring, cables, conduits or other equipment until the same has been inspected and approved by an electrical inspector.
|
Issue PAID IN FULL permit | | | 7/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/16/2014 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|