First Notice | 7/24/2015 | 7/24/2015 | 5/13/2020 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by Deb Gooden
|
Final | 7/24/2015 | 7/24/2015 | 7/24/2015 | A | PASS |
Rex Boyles
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Inspection requested via web by Deb Gooden final ok on original groundwork permit
|
Electrical Rough-In | 10/14/2014 | 10/14/2014 | 10/14/2014 | P | FAIL |
Rock A. Hudson
|
|
|
###-#### Concrete encased rough in. 250.52(A)(3)- South east service, concrete encased will not work do to rebar and 20" of wire located on top of plastic moisture barrier, not tied to footing or foundation rebar. It shall be in direct contact with earth.
|
Electrical Rough-In | 10/13/2014 | 10/14/2014 | 10/14/2014 | A | NR |
Rock A. Hudson
|
|
|
Contact: Jeremy Thornock. Ufer inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Wire removed no rebar in place
|
Electrical Rough-In | 10/6/2014 | 10/7/2014 | 10/7/2014 | A | PASS |
Rock A. Hudson
|
|
|
Contact: Jeremy Thornock... underground rough-in inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Underground for south east electrical room rough in ok cover
|
Electrical Rough-In | 9/26/2014 | 9/29/2014 | 9/29/2014 | A | PASS |
Rock A. Hudson
|
|
|
Contact Name: Jeremy Thornock Underground Inspection Phone #: ###-#### Inspection requested via web by Deb Gooden Northwest electrical room underground rough in ok cover
|
Final | 7/17/2014 | 7/18/2014 | 7/18/2014 | P | NR |
Daryl DeGrange
|
|
|
Contact: Jeremy Thornock. inspection for 2 ufer grounds Phone #: ###-#### >> Inspection requested via web by Deb Gooden Not ready for final at this time.
|
Electrical Rough-In | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | PART |
Daryl DeGrange
|
|
|
Contact: Jeremy Thornock. inspection for 2 ufer grounds Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rough-in ok cover 1 of 2 concrete encased electrodes, northwest corner
|
Issue PAID IN FULL permit | | | 7/17/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/17/2014 | | |
|
|
|
|