Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE14-01976
StatusFinaled
Name EXTREME ELECTRIC
Site Address 4493 S CRUZATTE LN
Project Name171-1 Trailside
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Rough and Service
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/26/20148/26/20148/26/2014PPASS
DetailsBob Reichert
>> Inspection requested via web by Rowdy Monroe ok final
Rough-In Permanent Service7/23/20147/23/20147/23/2014PPASS
DetailsBob Reichert
>> Inspection requested via web by Rowdy Monroe corrections made, ri ok, p/s u/g n ok
Rough-In Permanent Service7/22/20147/23/20147/23/2014AFAIL
DetailsBob Reichert
171/1 Trailside Rough and service inspc.
thank you Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called, corrections not made, attic access, flush outside box
Electrical Rough-In7/21/20147/22/20147/22/2014AFAIL
DetailsBob Reichert
>> Inspection requested via web by Rowdy Monroe called, left correction notice, NEC 314.20 boxes shall be flush with finished surface, 110.12(B) shall not use broken boxes, 210.70(A)(3) shall provide lighting outlet under stairs, 334.30 shall not staple nm cable on edge, 334.23 shall protect nm cable within 6' of attic access, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member
Issue PAID IN FULL permit  7/21/2014 DONE
Payment received via Govolutions
Application received  7/21/2014 DONE
This permit was created on the web by Rowdy Monroe