Final | 8/26/2014 | 8/26/2014 | 8/26/2014 | P | PASS |
Bob Reichert
|
|
|
>> Inspection requested via web by Rowdy Monroe ok final
|
Rough-In Permanent Service | 7/23/2014 | 7/23/2014 | 7/23/2014 | P | PASS |
Bob Reichert
|
|
|
>> Inspection requested via web by Rowdy Monroe corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 7/22/2014 | 7/23/2014 | 7/23/2014 | A | FAIL |
Bob Reichert
|
|
|
171/1 Trailside Rough and service inspc. thank you Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called, corrections not made, attic access, flush outside box
|
Electrical Rough-In | 7/21/2014 | 7/22/2014 | 7/22/2014 | A | FAIL |
Bob Reichert
|
|
|
>> Inspection requested via web by Rowdy Monroe called, left correction notice, NEC 314.20 boxes shall be flush with finished surface, 110.12(B) shall not use broken boxes, 210.70(A)(3) shall provide lighting outlet under stairs, 334.30 shall not staple nm cable on edge, 334.23 shall protect nm cable within 6' of attic access, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member
|
Issue PAID IN FULL permit | | | 7/21/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/21/2014 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|