DOC - Permit Expired | 2/1/2019 | 2/1/2019 | 2/1/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Rough-In Permanent Service | 8/21/2014 | 8/21/2014 | 8/21/2014 | P | PASS |
Daryl DeGrange
|
|
|
Daryl: the floor has been raised and the pool lines in front of the panel are ready for inspection, any questions please let me know, thx! TW, The ACCESS CODE is 4780 Phone #: ###-#### Inspection requested via web by Stephen Kren correction done, Rough-in p/s u/g rec ok complete panel directory for final
|
Permanent Service | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | FAIL |
Daryl DeGrange
|
|
|
The access code is 4780, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 110.26(3)(F)(1)(a) Dedicated electrical space No piping below panel NEC 210.4(B) Common trip breakers for multiwire branch circuits NEC 240.24(A) Panel height NEC 250 250.56 upgrade service grounding 334.30 Securing NM cable within 12 in. of panel nail plates, KO plugs, Identify current carrying conductors
|
Issue PAID IN FULL permit | | | 7/25/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/25/2014 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|