Final | 11/4/2014 | 11/4/2014 | 11/4/2014 | P | PASS |
Rock A. Hudson
|
|
|
Nikoa Phone #: ###-#### Final ok
|
Final | 10/27/2014 | 10/28/2014 | 10/28/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Nikoa Phone #: ###-#### NEC 408.4 Panel directory not complete NEC 406.8(B)(1) GFCI receptacle for A/C unit requires weather resistant listing (WR) Double duplex receptacles in family room (grounging type) without equipment grounding conductor require GFCI protection. NEC 110.26 Clearance for A/C disconnect
|
Electrical Rough-In | 8/6/2014 | 8/7/2014 | 8/7/2014 | A | PASS |
Daryl DeGrange
|
|
|
Jordan Phone #: ###-#### Rough-in ok cover
|
Permanent Service | 8/7/2014 | 8/7/2014 | 8/7/2014 | A | PASS |
Daryl DeGrange
|
|
|
Jordan Phone #: ###-#### p/s o/h n ok
|
Electrical Rough-In | 8/5/2014 | 8/6/2014 | 8/5/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Jordan Phone #: ###-#### BCC and Idaho Power requirement Overhead service raiser, shall be 2 in.IMC if point of attachement NEC 250.96 Bonding of enclosures NEC 312.5(c) Cables shall be secured to cabnets, cutout boxes at entry NEC 200.6 Means of identifying grounded conductors
|
Conference | 7/30/2014 | 7/31/2014 | 7/31/2014 | A | DONE |
Daryl DeGrange
|
|
|
Doug wants to meet as well, please call him for appoint - Jordan Phone #: ###-#### Discussed with home owner elecetrical requirements for relocated single fmily dwellings.
|
Application received | | | 7/30/2014 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/30/2014 | | DONE |
|
|
|
|