Final | 7/15/2015 | 7/16/2015 | 7/16/2015 | A | PASS |
Bob Reichert
|
|
|
Installed gfi breaker for swim jet Phone #: ###-#### Inspection requested via web by Lars Johnson correction made, ok final
|
Final | 7/9/2015 | 7/9/2015 | 7/9/2015 | P | FAIL |
Eric Story
|
|
|
Swimming pool/spa - final Phone #: ###-#### Inspection requested via web by Lars Johnson 680.21 all 120v thru 240v pumps shall have GFCI protection
|
Electrical Rough-In | 8/25/2014 | 8/25/2014 | 8/25/2014 | A | PASS |
Bob Reichert
|
|
|
underground (low voltage lighting and equipment feeder Phone #: ###-#### >> Inspection requested via web by Lars Johnson called, u/g ok for lv lighting and feeder
|
Electrical Rough-In | 8/6/2014 | 8/6/2014 | 8/6/2014 | P | PASS |
Bob Reichert
|
|
|
Swimming pool/spa bonding: (1) equipment (1) slide (1) fence (1) swim jet bracket Phone #: ###-#### >> Inspection requested via web by Lars Johnson bonding ok per request
|
Issue PAID IN FULL permit | | | 7/31/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/31/2014 | | DONE |
|
|
|
This permit was created on the web by Lars Johnson
|