Final | 10/2/2014 | 10/3/2014 | 10/3/2014 | A | PASS |
Rex Boyles
|
|
|
Code CAM Phone #: ###-#### Inspection requested via web by Matthew White corrections made final ok
|
Final | 9/30/2014 | 10/1/2014 | 10/1/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Ryan Phone #: ###-#### NEC 210.8 (A)(7) All 15 and 20 ampere 120 volt receptacle within 6 ft. of an sink, basin require GFCI protection (kitchen) NEC406.4(D) Grounding type receptacle shall be connected to equipment grounding conductor.
|
Electrical Rough-In | 8/5/2014 | 8/6/2014 | 8/6/2014 | A | PASS |
Rock A. Hudson
|
|
|
Inspection requested via web by Matthew White Rough in ok cover
|
Issue PAID IN FULL permit | | | 8/5/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/5/2014 | | DONE |
|
|
|
This permit was created on the web by Matthew White
|