Final | 11/19/2014 | 11/20/2014 | 11/20/2014 | A | PASS |
Cevyn Recla
|
|
|
Ryan is contact ###-#### Phone #: ###-#### Inspection requested via web by Chris Chesnut corrections made, final ok
|
Final | 11/17/2014 | 11/17/2014 | 11/17/2014 | P | FAIL |
Cevyn Recla
|
|
|
spoke to contractor 440.52 overload protection to be sized to a/c units accordingly 110.26 working clearance about electrical equipment, a/c disconnects 422.31 Disconnecting means of permanently installed appliances, hood, micro, dishwasher 210.8A5 GFI protection required unfinished basemnet 410.16B. luminaire clothes closet, no open lamp fixtures allowed 362.30B. strap riser within 3 ft. of meter BCC 4.05.26 all work to be complete for inspection-missing plate in living room cabinet, bedroom light not working BCC. Energy Code, 50% minimum of fixtures to be of energy efficient type.
|
Final | 11/12/2014 | 11/13/2014 | 11/12/2014 | P | CANC |
Bob Reichert
|
|
|
Ryan Wake is contact Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Inspection cancelled from web by: Chris Chesnut
|
Electrical Rough-In | 8/13/2014 | 8/13/2014 | 8/13/2014 | P | PASS |
Bob Reichert
|
|
|
Ryan is contact. No permanent service......yet
Thanks! Phone #: ###-#### >> Inspection requested via web by Chris Chesnut ri ok
|
Issue PAID IN FULL permit | | | 8/13/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/13/2014 | | DONE |
|
|
|
This permit was created on the web by Chris Chesnut
|