First Notice | 8/28/2014 | 8/28/2014 | 9/9/2014 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by kendall bender
|
Final | 8/28/2014 | 8/28/2014 | 8/28/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender corrections made, ok final
|
Final | 8/20/2014 | 8/21/2014 | 8/21/2014 | A | NR |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender See rough in
|
Electrical Rough-In | 8/20/2014 | 8/21/2014 | 8/21/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.63- A 120 volt 15 or 20 amp receptical outlet shall be located with in 25' of outdoor unit. 334.12- NM cable in seal tight not rated for damp location. BCC NM cable not permitted for church wiring. Unable to verify 15 amp max fuse.
|
Issue PAID IN FULL permit | | | 8/20/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/20/2014 | | DONE |
|
|
|
This permit was created on the web by kendall bender
|