Final | 10/23/2014 | 10/23/2014 | 10/23/2014 | P | PASS |
Rock A. Hudson
|
|
|
The corrections have been fixed, any questions please let me know, thx, TW the ACCESS CODE is 6949 (for both homes) Phone #: ###-#### Inspection requested via web by Stephen Kren
|
Final | 10/17/2014 | 10/20/2014 | 10/20/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 110.3 Wiring under sink shall be completed
|
Rough-In Permanent Service | 9/12/2014 | 9/12/2014 | 9/12/2014 | P | PASS |
Rock A. Hudson
|
|
|
Daryl knows about this one, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Service available fault current 18k rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 8/26/2014 | 8/28/2014 | 8/28/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Any questions pleas let us know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Service failed NEC 110.9 Interrupting rating required for available fault current. service close to 100 KVA transformer
|
Electrical Rough-In | 8/28/2014 | 8/28/2014 | 8/28/2014 | A | PASS |
Daryl DeGrange
|
|
|
Any questions pleas let us know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Rough-in ok cover
|
Issue PAID IN FULL permit | | | 8/26/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/26/2014 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|