Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE14-02458
StatusFinaled
Name CONLEY ELECTRIC
Site Address 6521 W USTICK RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Remodel store space for storage and minor kitchen use
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice12/11/201412/11/201412/18/2014 DONE
DetailsRock A. Hudson
This permit finaled on the web by Don Conley
First Notice12/11/201412/11/201412/18/2014 DONE
DetailsRock A. Hudson
This permit finaled on the web by Don Conley
Final12/11/201412/12/201412/11/2014APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Don Conley Corrections made. Final ok
Final12/11/201412/11/201412/11/2014PPASS
DetailsRock A. Hudson
Corrections made. Final ok
Final12/10/201412/11/201412/11/2014AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Don Conley Verbal with Troy. GFCI protection for drinking fountain, and all 120 volt receptical outlet located in kitchen area.
Permanent Service12/5/201412/5/201412/5/2014PPASS
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by Don Conley correction made, p/s o/h n ok
Permanent Service12/4/201412/4/201412/4/2014PFAIL
DetailsBob Reichert
Garage code for the back 1668 if no one is there. Call Troy at ###-#### with any questions Phone #: ###-#### Inspection requested via web by Don Conley called, left message, NEC 110.24 shall post available fault code at service, shall remove existing service for 6 service drops
Electrical Rough-In9/21/20149/22/20149/22/2014PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Don Conley Walls and hard lid rough in ok cover
Conference9/5/20149/5/20149/5/2014PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Don Conley Discussed energy efficient lighting , egress, emergency lighting required.
Issue PAID IN FULL permit  9/5/2014 DONE
Payment received via Govolutions
Owner Supplied Equipment  9/5/2014  
Application received  9/5/2014 DONE
This permit was created on the web by Don Conley