Final | 9/12/2014 | 9/12/2014 | 9/12/2014 | P | PASS |
Daryl DeGrange
|
|
|
Tom Phone #: ###-#### Correction completed, final ok
|
Permanent Service | 9/10/2014 | 9/11/2014 | 9/11/2014 | A | PASS |
Daryl DeGrange
|
|
|
Please call when done so I can fill in the trench Phone #: ###-#### Inspection requested via web by Thomas wilson p/s u/g rec ok ok cover trench no cover of skirting
|
Electrical Rough-In | 9/11/2014 | 9/11/2014 | 9/11/2014 | P | FAIL |
Daryl DeGrange
|
|
|
Please call when done so I can fill in the trench Phone #: ###-#### Inspection requested via web by Thomas wilson Cross over bonding (6) Thread-forming machine screws that engage not less than two threads in the enclosure 250.12 Clean Surfaces. Nonconductive coatings (such as paint, lacquer, and enamel) on equipment to be grounded shall be removed from threads and other contact surfaces to ensure good electrical continuity or be connected by means of fittings designed so as to make such removal unnecessary. II.
|
Issue PAID IN FULL permit | | | 9/9/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/9/2014 | | DONE |
|
|
|
This permit was created on the web by Thomas wilson
|