Final | 11/7/2014 | 11/7/2014 | 11/7/2014 | P | PASS |
Bob Reichert
|
|
|
Key pad is located at gate. Code is 5285. Phone #: ###-#### Inspection requested via web by Paula Gratiot corrections made, ok final
|
Final | 11/4/2014 | 11/6/2014 | 11/6/2014 | A | FAIL |
Cevyn Recla
|
|
|
Access is: Go to the gate on the right side of the residence. There is a keypad. Code is 5285. Return key when finished. Thanks Phone #: ###-#### Inspection requested via web by Paula Gratiot 312.5 B NM cable shall be bushed at opening 225.32 Disconnecting means shall be located at closest point of entrance to seperate building 334.15B Protection of romex -exposed out of framing members in garage 210.8A(5) GFI protection required in unfinished basements 210.52B2 no other receptacle supplied from small appliance circuit, range hood spoke to contractor
|
Electrical Rough-In | 9/12/2014 | 9/15/2014 | 9/15/2014 | A | CANC |
Daryl DeGrange
|
|
|
House will be unlocked for the inspection. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot rough-in ok cover
|
Issue PAID IN FULL permit | | | 9/12/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/12/2014 | | DONE |
|
|
|
This permit was created on the web by Paula Gratiot
|