Final | 3/25/2015 | 3/25/2015 | 3/25/2015 | P | PASS |
Daryl DeGrange
|
|
|
Cal Phone #: ###-#### No C/O card on site correction done, final ok
|
Final | 3/16/2015 | 3/17/2015 | 3/17/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Cal Phone #: ###-#### Inspection requested via web by cal crosby No access to living room and a bed in unit 101. 408.4- House panel each circuit shall be identified as to its purpose. 334.15(B)- NM cable shall be protected from physical damage. 200.6- White conductor shall be identified other than white at AC disconnects. Complete wiring for fire riser. 406.5- Receptacle outlets shall be securely mounted. outdoor receptacles.
|
Permanent Service | 10/13/2014 | 10/14/2014 | 10/14/2014 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by cal crosby p/s u/g n ok eight plex
|
Electrical Rough-In | 9/17/2014 | 9/17/2014 | 9/17/2014 | P | PASS |
Daryl DeGrange
|
|
|
the later the better, Thank you Phone #: ###-#### Inspection requested via web by cal crosby rough-in ok cover 8 plex no service at this time.
|
Conference | 9/16/2014 | 9/16/2014 | 9/16/2014 | P | DONE |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by cal crosby Met with contractor to do walk through on eight unit apartment .
|
Issue PAID IN FULL permit | | | 9/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/16/2014 | | DONE |
|
|
|
This permit was created on the web by cal crosby
|
First Notice | 3/25/2015 | 3/25/2015 | | | |
Daryl DeGrange
|
|
|
|