Final | 9/22/2014 | 9/23/2014 | 9/23/2014 | P | PASS |
Rex Boyles
|
|
|
10 solar panels. AC micro-inverter system. No DC voltage. A single home run, in conduit, is ran from solar array to the knife switch, located next to meter base in the back yard. From knife switch to breaker in main panel, at the bottom of busing, opposite the feeder lugs. This is an old split buss panel - so with the dead front on, the breaker appears to be in middle of panel, but is in fact at the end. The solar breaker is clearly marked, and its circuit number identified both in the knife switch and the panel schedule. The inverters, panels and rails are all bonded with a number 6 ground that runs back to the service ground in main panel.
Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King final ok
|
Issue PAID IN FULL permit | | | 9/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/16/2014 | | |
|
|
|
|