Final | 12/23/2014 | 12/24/2014 | 12/24/2014 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson corrections made, final oK
|
Final | 12/22/2014 | 12/23/2014 | 12/23/2014 | A | FAIL |
Cevyn Recla
|
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson left message for contractor BCC 4-05-26 TRIM-OUT (FINAL) INSPECTION Trim-out inspections shall cover the installation and/or connection of devices, cover plates, fixtures, utilization equipment
|
Final | 12/16/2014 | 12/17/2014 | 12/17/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson 110.7- Wiring integrity. Master bath vanity receptical outlet not working. Dead 300.15- Powder bath lighting outlet shall have box and cover. 406.5- Master vanity receptical outlets shall have covers. 410.16- Closet luminaires that can have incandescent lamps installed shall clear shelf by 12" minimum. up bed closets. 440.6- AC max overcurrent device shall not exceed that on name plate. 30 amp installed on 25 amp max.
|
Rough-In Permanent Service | 9/26/2014 | 9/29/2014 | 9/29/2014 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson r/i ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 9/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/16/2014 | | DONE |
|
|
|
This permit was created on the web by Zane Robertson
|