Final | 11/12/2014 | 11/12/2014 | 11/12/2014 | P | PASS |
Bob Reichert
|
|
|
1280 garage code Phone #: ###-#### Inspection requested via web by TOM BICANDI ok final
|
Rough-In Permanent Service | 9/24/2014 | 9/24/2014 | 9/24/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 9/23/2014 | 9/24/2014 | 9/24/2014 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI called, left correction notice, NEC 334.80 shall derate conductors over panel if more than 2 nm cables in hole, 334.23 shall protect nm cable within 6' of attic accesses, 210.52 shall install receptacle or floor box in 2' wall by pocket door, 300.4(A) edge of bored hole shall be 1 1/4" from face of framing member or add steel plate, BCC shall install wire into fan box
|
Issue PAID IN FULL permit | | | 9/23/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/23/2014 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|