Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE14-02656
StatusFinaled
Name BICANDI ELECTRIC LLC
Site Address 5788 E FELLY RIM CT
Project Name 
Customer Number989-8226
ePlanReviewNo
Description
Electrical Permit - New: New house
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/12/201411/12/201411/12/2014PPASS
DetailsBob Reichert
1280 garage code Phone #: ###-#### Inspection requested via web by TOM BICANDI ok final
Rough-In Permanent Service9/24/20149/24/20149/24/2014PPASS
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by TOM BICANDI ri ok, p/s u/g n ok
Rough-In Permanent Service9/23/20149/24/20149/24/2014AFAIL
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by TOM BICANDI called, left correction notice, NEC 334.80 shall derate conductors over panel if more than 2 nm cables in hole, 334.23 shall protect nm cable within 6' of attic accesses, 210.52 shall install receptacle or floor box in 2' wall by pocket door, 300.4(A) edge of bored hole shall be 1 1/4" from face of framing member or add steel plate, BCC shall install wire into fan box
Issue PAID IN FULL permit  9/23/2014 DONE
Payment received via Govolutions
Application received  9/23/2014 DONE
This permit was created on the web by TOM BICANDI