Final | 11/21/2014 | 11/21/2014 | 11/21/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ok final
|
Rough-In Permanent Service | 9/29/2014 | 9/29/2014 | 9/29/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 9/26/2014 | 9/26/2014 | 9/26/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.12(A) Unused Openings. Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or those permitted as part of the design for listed equipment, shall be closed to afford protection substantially equivalent to the wall of the equipment. Where metallic plugs or plates are used with nonmetallic enclosures, they shall be recessed at least 6 mm (1/4 in.) from the outer surface of the enclosure. 250.28 Main Bonding Jumper and System Bonding Jumper. For a grounded system, main bonding jumpers and system bonding jumpers shall be installed as follows: (A) Material. Main bonding jumpers and system bonding jumpers shall be of copper or other corrosion-resistant material. A main bonding jumper and a system bonding jumper shall be a wire, bus, screw, or similar suitable conductor. Screw missing. 590.6(B)- Dryer temp receptical shall have GFCI protection.
|
Issue PAID IN FULL permit | | | 9/26/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/26/2014 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|