First Notice | 10/31/2014 | 10/31/2014 | 12/8/2014 | | DONE |
Daryl DeGrange
|
|
|
|
Final | 10/30/2014 | 10/31/2014 | 10/31/2014 | A | PASS |
Daryl DeGrange
|
|
|
Bill Phone #: ###-#### correction done, final ok
|
Final | 10/29/2014 | 10/30/2014 | 10/30/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Bill Phone #: 608- NEC 110.4 No power ii S.W. office receptacle NEC 210.8(B)(5) Receptacles within 6ft of sink or basin NEC 422.52 Drinking fountain require GFCI protection
|
Electrical Rough-In | 9/29/2014 | 9/29/2014 | 9/29/2014 | P | PASS |
Daryl DeGrange
|
|
|
Bill Phone #: ###-#### correction done, rough-in ok cover
|
Electrical Rough-In | 9/26/2014 | 9/29/2014 | 9/29/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Bill Phone #: ###-#### NEC 330.12(1) NM cable shall not be installed less than 1 1/4 from nearest edge of framing member or stud. NEC 330.30(B) MC cable shall be secured within 12in. of every box, cabnet.
|
Application received | | | 9/26/2014 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/26/2014 | | DONE |
|
|
|
|