First Notice | 6/24/2015 | 6/24/2015 | 12/2/2015 | | DONE |
Rex Boyles
|
|
|
|
Print Statement | | | 12/2/2015 | | DONE |
|
|
|
|
Final | 6/23/2015 | 6/24/2015 | 6/24/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins final ok
|
Final | 4/23/2015 | 4/23/2015 | 4/23/2015 | P | PART |
Rex Boyles
|
|
|
Temporary final for job. Looking for final on metal building wash bay to be done at later time. Phone #: ###-#### Inspection requested via web by Thomas Jenkins 406.8(B)-15 and 20 amp exterior receptacles shall be UV rated. 110.16-All electrical equiptment , loadcenters,etc shall have arc flash label clearly visable. HVAC equiptment "maximum fuse" exceeded on some equiptment. Panel directory not accurate.TEMP. OCCUPANCY OK. REX GAVE THE OK TO CHANGE TO A PART blh 5-1-15
|
Electrical Rough-In | 2/18/2015 | 2/19/2015 | 2/19/2015 | A | PASS |
Rex Boyles
|
|
|
underground Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i u.ground ok to car chargers and grounding electrode conductor at wash bay ok
|
Electrical Rough-In | 2/13/2015 | 2/13/2015 | 2/13/2015 | A | PASS |
Rex Boyles
|
|
|
Underground Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i u.ground to wash bay and R&D area ok
|
Electrical Rough-In | 2/11/2015 | 2/12/2015 | 2/12/2015 | A | PASS |
Rex Boyles
|
|
|
underground and uffer fix. Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i u.ground east outside slab ok. Look for #4 ufer on next insp. to bldg. footing
|
Permanent Service | 2/2/2015 | 2/3/2015 | 2/3/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins p/s u/g n ok verify ground conductor to bldg. steel and water pipe and plastic bushings inside transformer upon return. Also picture of grounding electrode to concrete footing connection.
|
Electrical Rough-In | 2/2/2015 | 2/3/2015 | 2/3/2015 | A | PASS |
Rex Boyles
|
|
|
Rough for change order work. Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i main bldg. walls ok r/i underground ok inside wash bay bldg.
|
Electrical Rough-In | 1/15/2015 | 1/16/2015 | 1/16/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i walls ok
|
Electrical Rough-In | 10/8/2014 | 10/8/2014 | 10/8/2014 | A | PASS |
Rock A. Hudson
|
|
|
Please call 30 min before you get there so someone can meet you there to let you in. Phone #: ###-#### Inspection requested via web by Thomas Jenkins All underground in main bldg and 1 in small pull thru bldg rough in ok cover
|
Conference | 10/6/2014 | 10/6/2014 | 10/6/2014 | P | DONE |
Rock A. Hudson
|
|
|
Conference to figure out ufer ground Phone #: ###-#### Inspection requested via web by Thomas Jenkins Concrete encased and building steel are grounding electrodes for this service. 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding (3) Concrete-Encased Electrode. A concrete-encased electrode shall consist of at least 6.0 m (20 ft) of either (1) or (2): (1) One or more bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or rods of not less than 13 mm (1/2 in.) in diameter, installed in one continuous 6.0 m (20 ft) length, or if in multiple pieces connected together by the usual steel tie wires, exothermic welding, welding, or other effective means to create a 6.0 m (20 ft) or greater length; or (2) Bare copper conductor not smaller than 4 AWG
|
Issue PAID IN FULL permit | | | 9/30/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/30/2014 | | DONE |
|
|
|
This permit was created on the web by Thomas Jenkins
|