Temporary Service | 10/1/2014 | 10/2/2014 | 10/2/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Idsinga t/s o/h n ok
|
Temporary Service | 10/1/2014 | 10/1/2014 | 10/1/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Its the tall pole at Jackson across from the store. Phone #: ###-#### Inspection requested via web by Greg Idsinga 250.80 Service Raceways and Enclosures. Metal enclosures and raceways for service conductors and equipment shall be connected to the grounded system conductor if the electrical system is grounded. 250.92(B) Method of Bonding at the Service. Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s).
|
Issue PAID IN FULL permit | | | 10/1/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/1/2014 | | DONE |
|
|
|
This permit was created on the web by Greg Idsinga
|