Temporary Service | 10/11/2014 | 10/13/2014 | 10/13/2014 | P | PASS |
Rock A. Hudson
|
|
|
please call before going ###-#### Phone #: ###-#### Inspection requested via web by Lori Stout t/s o/h n ok
|
Temporary Service | 10/9/2014 | 10/10/2014 | 10/10/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lori Stout 400.5(A)- Flexible cord shall be protected by overcurrrent device sized in accordance with table 400.5 (A). #8 cord on 35 amp max. 550.11(D)- JOb trailer shall have feeder sized to electrical installed on trailer. 100 amp min. Nameplate not found. 590.6(B)- Receptical outlets including cord connectors shall have GFCI protection or comply with 590.6(B)(2).
|
Issue PAID IN FULL permit | | | 10/9/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/9/2014 | | DONE |
|
|
|
This permit was created on the web by Lori Stout
|
First Notice | 10/13/2014 | 10/13/2014 | | | |
Rock A. Hudson
|
|
|
|